PVI Industries Water Heater 119 Gallon Tank Series User Manual |
LOW NOx MAXIM • PACKAGED GAS WATER HEATER
POLYSHIELD® POLYMER-LINED STORAGE TANK
119 GALLON TANK SERIES
20 P 119A-MXS
MODEL NUMBER
GPH Recovery at 40° to 120° F
GPH Recovery at 40° to 140° F
Input Btu/h
245
195
199,000
Minimum gas inlet pressure – " W.C.
Cold Inlet - NPT
Hot Outlet - NPT
Drain - NPT
I - Beam Skids
5.5
2
2
A
B
C
D
E
F
1
3 X 34-1/2
47
Overall Depth
Overall Height
75
G
H
J
Flue Outlet Diameter
Gas Inlet - NPT
Motor HP 120 V, 1Ø, 60 Hz.
Motor Amps
5
1/2
1/6
1.75
65
L
Height to Outlet
M
Height to Inlet
28
Approx. Shipping Weight - lbs
1070
1. Control Enclosure
2. ASME Temperature &
Pressure Relief Valve
3. 3” NPT Handhole
Recoveries based on 82% thermal efficiency. ASHRAE 90.1 compliant.
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see Form # PV6377.
34 1/2
41
G
1
B
2
A
3
F
L
H
M
C
J
D
23
E
STANDARD GAS PRESSURE REQUIREMENTS:
VENTING REQUIREMENTS:
-.02" TO -.06" W.C. (NEGATIVE PRESSURE).
TYPE B VENTING.
THE ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE
VENT CONNECTION DIAMETER EXCLUSIVELY.
FOR PROPER VENT SIZING, CONSULT THE NATIONAL FUEL GAS CODE
UNDER "FAN-ASSISTED".
SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER.
MAXIMUM STATIC PRESSURE: 9" W.C.
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,
CONTACT YOUR PVI REPRESENTATIVE.
STANDARD ELECTRICAL REQUIREMENTS:
CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND
SPECIFICATION WITHOUT NOTICE.
Product is patented in the U.S., Canada, and Mexico.
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111
PV 6433 01/06
|